9.10. Verification and adjustment of
the reading index
To verify or to adjust the reading index, in
particular after having renewed a tape, apply the
following instruction:
-
if the equipment is fitted with a 2" connector
(Q2) remove the clip and the collar as shown
-
unlock and remove the lid of the tape housing;
-
put the tape cleaner on "DOWN" position;
-
keep the equipment standing vertically on a
flat surface;
-
gently lower the tape until the sensor touches
the surface (Figure 10-11);
-
adjust the index to the value corresponding to
the connector Q1 or Q2, as shown on Figure
-
In case of a 2" connector (Q2) put back the
clip and the collar .
-
Put the housing lid back and lock it.
IMPORTANT NOTE: these adjusting values for
the reading index are different from the heights
shown in the section 8 "Examples of installation of
the gauging system". They take into account the
recessment of the reaction point from the sensor
tip end and other mechanical parameters.
Figure 10-11