How to start or stop a 'Weekly test'
On starting a weekly fire test function the system enters the zone test mode and identifies the next device to be tested. You will need to be at access level 2 or above to stop or start weekly test.
Commissioning instructions
60
4188-949 issue 3_05/10_Nano Comms inst.
How
to
s
tart
or
stop
a
'Weekly
test'
Menu
Start/Stop
Select
System
>
Select
User
Weekly
Test
Select
Select
10:15 Tue 16/02/10
Start Weekly Fire Test
Warning!
Selecting 'FIRE TEST’ causes all
zones to enter test state
A
?
Yes
NO
RE YOU SURE YOU WANT TO PROCEED
10:15 Tue 16/02/10
Stop Weekly Fire Test
Warning!
Stopping ‘FIRE TEST’ will cause all
zones to leave the test state
A
?
Yes
No
RE YOU SURE YOU WANT TO PROCEED
Weekly Fire Test
10:15 Mon 16/02/10
ALL ZONES IN TEST STATE
Next manual call point to be tested
Dv 004
Device 4
Zn 001
Zone 1
+/- More
Quit
Stop
weekly
test
Start
weekly
test
Yes
Yes
Test
Test
Only the ALARM sectors are
actioned in Test, The PLANT
sectors are not affected.
Audible
Buzzer
AUTOMATIC
Silence
Alarms
AUTOMATIC
Reset
After a short
duration.
On
Flashing
Manual Call point
Test Key
Audible
Buzzer
ZONE 1
FIRE
(red LEDs)
First fire indication
(flashing LED)
Common fire LED
(Steady indication)
FIRE MESSAGE
key
Device to be tested
Test Fire
Alarm
The PLANT equipment will not
operate during ‘Fire Test’ condition.
Green LED
ZONE 1
FIRE
First fire indication
(flashing LED)
Common fire LED
(Red - Steady indication)
Test Fire
Alarm
TEST FIRE
After a short
duration.