How to set-up the 'Class Change input'
The class change input application is used in schools to output a class change alarm via the sounders in selected sectors to signify end of class.
You will need to be at access level 3 or above to configure class change input.
You will also need to assign class change to activate sectors see section headed 'How to set-up 'Sector' mode, label and activation'.
Commissioning instructions
56
4188-949 issue 3_05/10_Nano Comms inst.
How
to
set-up
the
'Class
Change
input'
10:15 Tue 16/02/10
External Input Settings
External Evacuate Input Used
: [NO ]
External Evacuate Input Latches : [NO ]
Class Change Input Used
: [NO ]
Save
Quit
External
Inputs
Select
Set the ‘Class Change’ input
use requirement to - ‘NO’ (factory default setting) or ‘YES’
Save
More
>
Select
Select
System
>
Select
Settings
Menu
To scroll the
settings
To move to the
class change
field
After making changes to this form you will need to back-up the data to
memory. Ensure the write protect link P9 on the MCB is configured in
the ENABLED position to allow back-up of data.
Class Change
2 - 10K Ohms -
resistors must be
fitted as shown.
+VE
0V
DRN
CLASS CHANGE
PP8
Switch
Normally open contacts
CLASS CHANGE ALARM
To stop the class change alarms
simply release the switch.
by Honeywell
POWER
FAULT
FIRE
Test
Delay
Verify
Sounder Fault
Zone 2
Zone 6
Zone 10
Zone 14
Zone 3
Zone 7
Zone 11
Zone 15
Zone 4
Zone 8
Zone 12
Zone 16
Disablement
Zone 1
Zone 5
Zone 9
Zone 13
System Fault
Sound
Alarms
Silence
Alarms
Power Fault
Reset
Cancel
Buzzer
Sounder
Disablement
042bc
EN54 Parts 2 & 4
12:30 Tue 16/02/10
[MENU]
Nano Fire Alarm System
Gent by Honeywell