How to view 'Diagnostics' data
The diagnostic data of mains, battery, loop, 24V supply, master alarm circuits, class change, external evacuate, earth and repeat indicator can be displayed for engineering use. This information is for
engineering use only and the illustration below show typical values. You will need to be at Access level 4 to view diagnostics data.
How to view 'Site data' version
The Site Data version number is a count of each upload of the configuration made from the Nano commissioning tool. You will need to be at access level 2 or above to view site data version.
4188-949 issue 3_05/10_Nano Comms inst.
29
Nano panel based system
How
to
v
iew
'Diagnostics'
data
10:15 Tue 16/02/10
Site Data Version Details
Version Number:
001
Last Updated:
16-02-2010
Back
Select
System
>
Select
Engineering
Menu
Versions
Select
Site
Data
Select
Back
Select
System
>
Select
Engineering
Diagnostics
Select
16:15 Fri 26/04/08
PSU Voltages
Mns
BtN
BtL
ChN
ChR
LpV
24V
207
207
206
255
031
196
047
MCB Voltages
MA1
MA2
Cls
Evc
Ear
24V
Rpt
086
084
127
128
090
205
209
Update
Back
Mains supply
Battery supply
Battery load test
Charger Nominal
Charger Recharge
Loop voltage
24V supply
Master alarm circuit 1
Master alarm circuit 2
Class Change
External Evacuate
Earth
24V supply
Repeat indicator
Update
Select ‘Update’ to refresh the voltage values.
Menu