How 'Cause and Effect' interact with 'Day and Night Modes'
This page illustrates the immediate and delayed Cause and Effect interaction with Day and Night modes.
¨
The immediate actions of a zone will always occur immediately in the event of a fire from the zone regardless of Day/Night mode status.
¨
The delayed actions of a zone will occur after the day mode delay has timed out when 'Day mode' is active. Additional verify delay will apply if it is set up and made active
during day mode delay.
"
By configuring the immediate actions same as delayed actions it is possible to use the Day/Night mode switching to switch sensor sensitivity states.
4188-949 issue 3_05/10_Nano Comms inst.
45
Nano panel based system
How
'Cause
a
nd
Effect'
interact
with
'Day
and
N
ight
Modes'
‘Day mode’
active
Delay
‘Day mode’
inactive
Delay
Zone ‘Immediate C&E’
Master
Alarms
Fire
Relay
Factory Default actions
(Can be changed to custom settings)
Zone ‘Delayed C&E’
Master
Alarms
Fire
Relay
Zone ‘Delayed C&E’
Master
Alarms
Fire
Relay
Fire Event
Fire Event
Delay can be
up to
10 minutes max.
(Factory default
is 30 seconds).
No action
No action
No action
Action
Action
Evacuate
Action
Action
Action
Evacuate
Action
Sectors
Sectors
Sectors
Zone ‘Immediate C&E’
Master
Alarms
Fire
Relay
No action
No action
No action
Sectors
The final output after the delay
is the amalgamation of
of both Immediate and Delayed C&E.
ACTIVE HIGH PRIORITY ACTIONS
Factory Default actions
(Can be changed to custom settings)
The final output is the
amalgamation of
of both Immediate and Delayed C&E.
ACTIVE HIGH PRIORITY ACTIONS
C&E - Cause and Effect
Night
mode
Day