How to 'Enable' or 'Disable' a Zone
You can manually disable a zone to prevent system going into a fire condition in the event of a fire being detected in the zone. ~You can reenable the disabled zone at anytime. You will need to be at
Access level 2 or above
How to place a Zone in 'Test Mode'
The Zone 'Test mode' function is used when testing devices in a zone. It allows the engineer to test zones without having to return to the panel to silence alarms and reset.
While the panel is in the Zone Test mode and following a fire event the alarm sounds for 5 seconds and then automatically performs the silence alarm sequence and thereafter a panel reset. The panel
inhibits the operation of delays and fire relay. For information on how to conduct a fire test see page 60.
¨
All zones of the system that are not in test mode will operate normally.
"
On completion of all commissioning work, switch Off the Zone Test mode and notice the Test indicator also switches Off.
4188-949 issue 3_05/10_Nano Comms inst.
61
Nano panel based system
How
to
'Enable'
o
r
'Disable'
a
Zone
10:15 Tue 16/02/10
Zone : [01]
Label: Zone Label
Status : [ ENABLED ]
Test : [ NO ]
Save
Quit
Select a ‘Zone’ from a range 1 to 16
Select the ‘Zone’ status:
Zone ‘ENABLED’ (factory default setting)
or Zone ‘DISABLED’
Save
Menu
Select
Zones
Select
User
To scroll the
range
To move to
the next setting
Disablement
[amber LED]
10:15 Tue 16/02/10
Zone : [01]
Label: Zone Label
Status : [ ENABLED ]
Test : [ NO ]
Save
Quit
Place the ‘Zone’ in to ‘Test mode’ - NO (factory default setting) or YES
Select a ‘Zone’ from a range 1 to 16
Save
Menu
Select
Zones
Select
Select
User
To scroll the
range
To move to
the next setting
Test
[amber LED]
Only the ALARM sectors are
actioned in Test, the PLANT
sectors are not affected.