How to restore 'Config', 'Labels' or 'Logo' from a SD card
A previously saved system configuration data, labels and proprietary Logo file on a SD card can be restored to the panel. You will need to be at access level 4 to load configuration stored on a SD card.
How to use a SD card to log 'Historic Events' for diagnostics
Up to
64 million historic events
can be stored on to a
1G byte regular SD card
when it is left inserted in the SD card slot on MCB. The SD card must have a folder named
nanologs
to enable the
panel to create and store historic log to a text file in the folder. The text file on the SD card can be opened and viewed via a card reader connected to a PC. The historic log of the panel is unaffected by
the introduction of SD card to keep a large store of historic events.
4188-949 issue 3_05/10_Nano Comms inst.
69
Nano panel based system
How
to
restore
'Config',
'Labels'
or
'Logo'
from
a
S
D
card
Ensure the SD card is fitted into the Main Control Board.
Select
Maintenance
>
Select
Select
Engineering
Menu
SD
Card
Select
Select
Restore
After configuration is restored you will need to back-up the data to
memory. Ensure the write protect link P9 on the MCB is configured in
the ENABLED position to allow back-up of data.
Main Control Board
SD card
DO NOT remove the SD card
while the RED LED is flashing.
RED LED
Select
16:15 Tue 16/02/10
This will load the labels
data from your SD card!!
Are you sure?
Yes
No
Yes
Labels
Select
16:15 Tue 16/02/10
This will load the configuration
data from your SD card!!
Are you sure?
Yes
No
Yes
All
Select
16:15 Tue 16/02/10
This will load the logo
data from the SD card!!
Are you sure?
Yes
No
Yes
Logo
Select