How to view Sensor 'Condition Codes'
The condition codes provide information about a sensor device. A code indicates small changes in the environmental condition, sensor mechanism and how the sensor performs in the system. You will
need to be at access level 4 to view sensor condition codes.
To ensure that the sensor condition codes are meaningful, all existing codes must be cleared and the system left undisturbed for at least 24 hours. To clear the condition codes Power-down and then
Power -up the loop and then Start Detection, see page 24. Alternatively use the clear condition codes option on each device that currently has a code.
Code definition
There are ten different conditions possible for each sensor type, although not all of them are defined. Each condition code has a range of 0-3.
Condition
Code
Meaning
0
This condition is OK.
1 or 2
Suggests preventive maintenance is required, where necessary, to avoid possible false alarms.
3
The sensor is faulty. A fault condition indication is given at the control panel. A message reading ‘Sensor Out of Specification’ is displayed.
Commissioning instructions
52
4188-949 issue 3_05/10_Nano Comms inst.
How
to
v
iew
S
ensor
'Condition
Codes'
Select
Loop
>
Select
Select
Engineering
>
Menu
Map
Select
Select
View
Select
Select
Select
Conditions
Select
View
Codes
Codes
Select
Select
Reset
Codes
Select
16:15 Tue 16/02/10
Reset Condition Codes
WARNING! - This option will reset the
Condition Codes for the Selected
device.
?
Yes
No
ARE YOU SURE YOU WANT TO PROCEED
10:15 Tue 16/02/10
Loop Map
1*
Device
1
2
Device
2
3
Device
3
4
Device
4
Select
Quit
9
9
9
9
Yes
DEVICE
10:15 Tue 16/02/10
Device [
1] Condition Codes
CC0 CC1 CC2 CC3 CC4 CC5 CC6 CC7 CC8 CC9
0
0
0
0
0
0
0
0
0
0
Back
Back
CC0 CC1 CC2 CC3 CC4 CC5 CC6 CC7 CC8 CC9
0
0
0
0
0
0
0
0
0
0
Condition Code position number
Refer to the table for S-Quad
devices for meaning
Condition Codes
An * after the device number signify the
device has a Condition Code