Enhanced Micro TDC 3000 User’s Manual
6-3
9/95
6.1
Table 6-1 lists node types which can be installed in the Enhanced Micro TDC 3000 Control
System. In addition, the table lists the factory-assigned node numbers and the board slots
where those node types are found. For details about specific boards used in each option,
consult the 8-Node Multinode Module Service manual in the Implementation/8-Node
Enhanced Micro TDC 3000 binder.
Table 6-2 — Enhanced Micro TDC 3000 Node Numbers and Node Types
LCN
NO.
UCN
NO.
NODE TYPES
TOWER
BOARD
SLOTS
5
AM—Application Module
#1*
7, 8
1
US—Universal Station
#1
1, 2
3
1
NIM—Network Interface Module
#1
9,10
6
HM—History Module
#2*
7,8
2
US—Second Universal Station
#2
1, 2
7
US—Third Universal Station (optional)
#1, 2
4, 5
8
US—Fourth Universal Station (optional)
#1
4, 5
4
2
NIM—Redundant NIM (optional)
#2
9,10
7
CG—Computer Gateway (optional)
#2
4, 5
10
NG—Network Gateway (single cable)
11
NG—Network Gateway (dual cable)
12
PLCG—Programmable Logic Controller
Gateway (optional)
#1, 2
4, 5
13
EPLCG—Enhanced Programmable Logic
Controller Gateway (optional)
14
PNM—Plant Network Module
3
APMM—Adv. Proc. Mgr Mod. (Primary)
4
APMM—Adv. Proc. Mgr Mod. (optional
Secondary)
* Right Tower is #1 and Left Tower is #2
The touchscreen, trackball, keyboards, hard drive/power supply, cartridge drive, printer,
printer-head, printer ribbon, and air filters are ORU (Optimum Replaceable Unit) items and
are replaced when found faulty. Refer to the spare parts list in subsection 6.5 and to the
Universal Station Service in the LCN Service - 1 binder for their order numbers.
Multinode Module parts which include the 3/3/2/2 cardcage, power supply, fan assembly,
and circuit cards are also replaced at the ORU level. For these parts, refer to the spare parts
section in the 8-Node Multinode Module Service manual in the Implementation/8-Node
Enhanced Micro TDC 3000 binder.
Although cables and power cords are not considered ORU items, their part numbers are
listed in the spare parts section for reference.
Summary of Contents for Enhanced Micro TDC 3000
Page 1: ...L 8 Node Enhanced Micro TDC 3000 User s Manual MT11 520 ...
Page 2: ......
Page 10: ...Enhanced Micro TDC 3000 User s Manual iv 9 95 ...
Page 56: ...Enhanced Micro TDC 3000 User s Manual 3 8 9 95 ...
Page 82: ...Enhanced Micro TDC 3000 User s Manual 4 26 9 95 ...
Page 128: ...Enhanced Micro TDC 3000 User s Manual 5 46 9 95 ...
Page 144: ...Enhanced Micro TDC 3000 User s Manual 6 16 9 95 ...
Page 156: ...Enhanced Micro TDC 3000 User s Manual B 4 9 95 ...
Page 168: ...Enhanced Micro TDC 3000 User s Manual Index 12 7 95 ...
Page 171: ......