USER GUIDE
FALCON
63
EN2Z-0962GE51 R0715
Editing
x
Equivalent
Generates and indicates the ´out of service` status of the datapoint. The ´out of
service` property allows decoupling the physical input or output from the datapoint.
For inputs the decoupling is done by manual override. For outputs this is done by
checking the ´Out of Service` flag.
The ´out of service` property is suited to fix the physical input or output state, e.g. in
case of maintenance checks.
In the following, the states of the ´out of service` flag/property of the various BACnet
objects are listed:
AI, BI, MI
Out Of Service = unchecked:
Present value has not been overwritten
Out Of Service = checked:
Present value has been overwritten
Present value is decoupled from the physical input and will not track changes to the
physical input.
AO, BO, MO
Out Of Service = checked:
Changes to the present value are decoupled from the physical output.
The present value property is still controlled by the prioritization mechanism (Priority
Array, Relinquish Default)
AV, BV, MV
Out Of Service = checked:
Present value is prevented from being modified by the application.
The present value property is still controlled by the prioritization mechanism (Priority
Array, Relinquish Default)
Pulse Converter
Out Of Service = unchecked:
Present value has not been overwritten
Out Of Service = checked:
Present value has been overwritten
Present value is decoupled from the Count property and will not track changes to
the input.
See also "In Alarm" and "Fault" sections.
Output NV
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
-
x
Equivalent
NV Type
Defines the network variable type (NVT) of the Lon point in CARE, e.g.
SNVT_lev_percent for an analog output point (NV - Output).
See also "Input NV" section.
Period
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Summary of Contents for Centraline FALCON
Page 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Page 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Page 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Page 9: ......
Page 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Page 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Page 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Page 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...