WEB BROWSER ACCESS VIA SERIAL INTERFACE (RS 232)
NOTE:
This function is not supported by Windows 7.
The Excel Web controller can be connected to the PC via the RS232 interface.
Connect the free COM port of PC to the port 2 of the Excel web controller by using a
null modem cable.
Null Modem Cable
http://192.168.253.20
Excel Web
Controller
IOIO 2
PC
Notebook, Touch panel PC, Desktop
COM
Fig. 10. Web Browser access via serial interface (RS 232)
Procedure
1.
From the Windows
Start
menu, select
Settings
, then N
etwork and Dial-up
Connections
.
RESULT: The
Network and Dial-Up Connections
window displays.
2.
Double-click on
Make New Connection
.
3.
In the
Network Connection Wizard
, click the
Next
button.