FALCON
USER GUIDE
EN2Z-0962GE51 R0715
158
Datapoints are selected/deselected from switching status by moving them
between the Assignable Datapoints and the
Switched Properties
list.
12.
To move datapoints between lists, that is, to make them switched or not, do one
of the following:
a. To move single datapoint(s),
Highlight the datapoint(s) to be moved in the
Assignable Datapoints
list.
Multiselection by using the CTRL or the SHIFT key is possible.
b. Or, click the checkbox at the point name in the
Switched Properties
list.
c. Click the SINGLE ARROW button with desired direction.
Or,
d. To move all datapoints in one step,
Click the DOUBLE ARROW button with desired direction.
13.
Under
Switched Properties
, select the property from the
Property
drop-down
list box for each datapoint.
NOTE: Software performs consistency checking for datapoint type, property
and engineering unit. This ensures that the engineering unit
corresponds to the property to be switched and prevents the same
schedule from switching
•
datapoints of different types (AO and BO), or
•
different properties (e.g. present value and low alarm limit) of
the same datapoint, or
If any of these items do not match, the corresponding lines are marked
with an inconsistency warning.
14.
To save settings, click the OK button.
RESULT:
The
New / Edit Schedule
dialog box displays.
Summary of Contents for Centraline FALCON
Page 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Page 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Page 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Page 9: ......
Page 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Page 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Page 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Page 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...