RESULT:
On the
Event Enrollments
tab, you can select event enrollments
to enable the controller´s system status alarming and the
alarming of the controller´s Email alarming:
3.
To enable event enrollment alarming for the controllers email alarming, click the
EmailAlarming
link. To enable event enrollment alarming for the controller´s
system status, see “Enable Event Enrollment Alarming for Controller System
Status” section.
RESULT:
After selecting the
System Status
event enrollment, the
Event
Enrollment Details
dialog box displays. The
Alarming
tab is
selected by default. Here the following algorithmic reporting
settings defined in CARE are displayed:
•
Notification Class
•
Notify Type
•
Event State
•
Transitions (Acknowledged status and time and date of last
transition)
•
Event Type
•
BACnet Property State
•
BACnet Device State(s) (=Off-Normal-States)
You only can select the transitions to be reported and set the