Purpose
Allows observing the acknowledgement behavior of a user for To-Off-Normal and
To-Fault transition events of the datapoint. CARE checks whether a transition event
has been acknowledged or not. If a transition event has not been acknowledged
within a definable delay time, an alarm based on an event enrollment (event
enrollment alarm) is sent to a supervisory recipient, for example EBI.
Procedure
1.
In the
Details
dialog box of the selected datapoint, select the
Event Enrollments
tab.
Here you can select different event enrollments for viewing and edting. Each
event enrollment is displayed as link. By default, event enrollments have the
following naming convention <EE = event enrollment> <datapoint type
abbreviation> <event enrollment type>, for example EE ai. AckedTransitions.
2.
To view/edit an event enrollment, click the event enrollment, for example EE ai.
AckedTransitions. The
Details
dialog box for the selected event enrollment
displays. The
Alarming
tab is selected by default.
Algorithmic Reporting
•
Notification Class
Shows the name of the notification class. The value in brackets is the
BACnet object ID of the notification class.
•
Notify Type
Shows the notify type. Defaults to ´event`. For details, see Notify Type
property description
•
Event State
Shows the event state. For details, see Event State property description.
•
Transitions
Here the following data about transitions are shown:
Summary of Contents for Centraline FALCON
Page 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Page 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Page 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Page 9: ......
Page 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Page 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Page 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Page 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...