FALCON
USER GUIDE
EN2Z-0962GE51 R0715
58
States
In Alarm
Alarm Text Display
1
NO
NO
2
YES
YES
See also "Is in Alarm" section.
Increment
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
x
x
Equivalent
Change of Value Increment
The change of value increment (COV increment) specifies the minimum change in
present value that causes the controller sending the present value to recipients on
the BACnet bus (e.g. Excel Web HTML Interface, EBI).
The COV increment is also used as the minimum change in the present value for
value-based trending.
NOTE: For the pulse convertor point type, a time-based COV increment is
possible.
Usage with Reference Inputs
When using reference input points which read input values, the inputs can be reside
either in different plants of the same controller (internal referencing) or in plants of
different controllers (external referencing).
If the reference input point reads values from an internal referencing plant, the
original datapoint value of the input will be taken.
If the reference input point reads values from an external referencing plant, a copy
of the original datapoint value of the input will be taken. Please note, that in this
case, the COV value must be set to appropriate (low) values in order to minimize
falsification of the transmitted value.
Initial Value
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
x
Equivalent
For reference input points, an initial value can be entered, which will be utilized at
system startup if the reference input has not yet received a value from the
connected point.
Input NV
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
-
x
Equivalent
NV Type
Defines the network variable type (NVT) of the Lon point in CARE, e.g. SNVT_temp
for an analog input point (NV - Input).
See also "NV Type" section.
Summary of Contents for Centraline FALCON
Page 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Page 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Page 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Page 9: ......
Page 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Page 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Page 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Page 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...