USER GUIDE
FALCON
99
EN2Z-0962GE51 R0715
Alarm and Event Priority Classification
Alarms and events traversing the BACnet network need prioritization to assure that
important information reaches its destination and is acted upon quickly. To assure
alarm prioritization at the network level, the network priority as defined in the
n
etwork
layer protocol control is set automatically according to the alarm and event
priority settings (see following table).
Alarm and Event Priority
Network Priority
Association
00 – 63
Life Safety message
64 - 127
Critical Equipment message
128 - 191
Urgent message
192 - 255
Normal message