Installation Instructions / ACS-8
DIP switches:
DIP switch S1 can be used to switch off selected bus lines allowing an additional security feature to function.
This allows the ACS-8 to de-activate selected lines following a trigger event.
With all switches in the OFF position (factory setting) all the RS 485 lines are active. Any lines whose DIP switch
is set to ON can be deactivated by the ACS-8. This prevents any tampering affecting the other data buses from
the communication module.
Switch / line allocation:
Switch block
Switch
Line
Communication module
Terminals
S1
1
1
1
1, 2, 3
S1
2
2
1
6, 7, 8
S1
3
3
2
1, 2, 3
S1
4
4
2
6, 7, 8
S1
5
5
reserved, remains OFF
S1
6
6
reserved, remains OFF
DIP-switch 2 of the communication module has to retain its factory settings in the current version (see table).
Additional planned features have not been implemented to date.
Switch block
Switch
Position
Function
S2
1
ON
Factory settings
S2
2
OFF
S2
3
OFF
S2
4
OFF
Terminal assignment:
RS 485
bus
Terminal
Designation
1
1
0V
2
D
3
D*
2
6
0V
7
D
8
D*
Summary of Contents for ACS-8
Page 2: ... VdS Approval Z 105009 class C ...
Page 16: ...16 Installation Instructions ACS 8 ...
Page 28: ...28 Installation Instructions ACS 8 ...
Page 29: ...Installation Instructions ACS 8 29 ...
Page 76: ...76 Installation Instructions ACS 8 Connection component mounting diagram ...
Page 92: ...92 Installation Instructions ACS 8 15 2 ACS 8 Structure ...
Page 122: ...122 Installation Instructions ACS 8 Connection diagram for 026064 Keypad sm plastic housing ...
Page 123: ...Installation Instructions ACS 8 123 ...
Page 124: ...124 Installation Instructions ACS 8 ...
Page 130: ...130 Installation Instructions ACS 8 ...
Page 140: ...140 Installation Instructions ACS 8 ...