Installation Instructions / ACS-8
97
16.5 Electric safety lock
The electric safety lock is available in a conventionally connectable variant (809) as well as in a BUS version (809N).
16.5.1
Electric safety lock conventional connection
The differential monitored inputs (inputs 5 - 10) must be terminated with 12K
Ω
resistor.
An additional third and/or fourth door can not be connected because input 6 is in use with
this connection.
Door monitoring
The interior door handle contact effects a door release through the ACS-8. The door can
be opened without the error message “Unauthorized door release”.
An external contact, e.g. a magnetic contact, must be used for door monitoring. The state
of the bolt switching contact is only polled when the intrusion detection system is
“disarmed”. Its status is therefore shown only when the intrusion detection system is
“disarmed”. The bolt switching contact alarm group does not trigger or store an alarm when
the intrusion detection system is “armed”.
Summary of Contents for ACS-8
Page 2: ... VdS Approval Z 105009 class C ...
Page 16: ...16 Installation Instructions ACS 8 ...
Page 28: ...28 Installation Instructions ACS 8 ...
Page 29: ...Installation Instructions ACS 8 29 ...
Page 76: ...76 Installation Instructions ACS 8 Connection component mounting diagram ...
Page 92: ...92 Installation Instructions ACS 8 15 2 ACS 8 Structure ...
Page 122: ...122 Installation Instructions ACS 8 Connection diagram for 026064 Keypad sm plastic housing ...
Page 123: ...Installation Instructions ACS 8 123 ...
Page 124: ...124 Installation Instructions ACS 8 ...
Page 130: ...130 Installation Instructions ACS 8 ...
Page 140: ...140 Installation Instructions ACS 8 ...