Installation Instructions / ACS-8
Module supply:
Total current consumption of the modules:
contactless / proximity reader (026390.10)
140mA
4I/2O-module (026592)
230mA
display module (027555)
150mA
keypad module (027570)
50mA
total:
570mA
Calculation of the maximum line resistance:
R
L
=
Uv
=
500mV =
0.877
Ω
I
570mA
Calculation of the maximum possible line length:
i
=
electrical conductivity
=
56m
of copper
Ω
mm²
L
= A x R
L
x
i
=
0.877 x 56m
=
24.556m
2
Ω
mm²
2
Power supply door strike:
Current consumption: 230mA
Calculation of the maximum line resistance:
R
L
=
Uv
=
500mV =
2.17
Ω
I
230mA
Calculation of the required cross-section:
i
=
electrical conductivity
=
56m
of copper
Ω
mm²
A
=
2 x L
=
2 x 24.556m
=
0.40mm²
R
L
x
i
2.17
Ω
* 56m
Ω
mm²
Calculation of the number of wires with a wire cross-section of 0.6mm (Ø 0.28mm²):
no. of wires
=
0.40mm²
=
1.42 wires
!
2 wires
0.28mm²
Summary of Contents for ACS-8
Page 2: ... VdS Approval Z 105009 class C ...
Page 16: ...16 Installation Instructions ACS 8 ...
Page 28: ...28 Installation Instructions ACS 8 ...
Page 29: ...Installation Instructions ACS 8 29 ...
Page 76: ...76 Installation Instructions ACS 8 Connection component mounting diagram ...
Page 92: ...92 Installation Instructions ACS 8 15 2 ACS 8 Structure ...
Page 122: ...122 Installation Instructions ACS 8 Connection diagram for 026064 Keypad sm plastic housing ...
Page 123: ...Installation Instructions ACS 8 123 ...
Page 124: ...124 Installation Instructions ACS 8 ...
Page 130: ...130 Installation Instructions ACS 8 ...
Page 140: ...140 Installation Instructions ACS 8 ...