118
Installation Instructions / ACS-8
Connection diagram for:
023330 - 023343
contactless proX2 reader Siedle
If only one reader is used, it is always connected as reader 1.
Terminal assignment ACS-8 :
Settings of the DIP switches located on the CPU board of the ACS-8 (see
chapter 9.6):
Switch
block
DIP
Setting
Designation
Reader
S2
1
OFF
Clock 1
Pull
down
1
2
OFF
Data 1
3
OFF
Clock 2
2
4
OFF
Data 2
5
ON
Clock 1
Pull up
1
6
ON
Data 1
7
ON
Clock 2
2
8
ON
Data 2