Installation Instructions / ACS-8
87
3
Except potetial separation module. There the LEDs indicate the communication between ACS-8 and module
bus participants.
For details see mounting and connection instaructions of potential separation module, P32508-10-002-xx.
Functions of the LEDs and the buzzer
of ACS-8 and module bus participants
3
LED/buzzer
State
Meaning
Normal (green)
Off
No operating voltage
Slow flashing
Not parameterized
Fast flashing
Parameterization running
On
Ready
Fault (yellow)
Off
No fault
On
Battery/battery fault
Line failure
Central reset
Without storing
(except for central reset)
Tamper (red)
Off
No tamper
On
Tamper
With storing
Alarm (red)*
Off
No alarm
On
Number of incorrect attempts
Unauthorized opening or door was open too
long
With storing
Alert (red)*
Off
No message
On
Threat
With storing
Buzzer
Off
No message or manually reset
Fast interval
Tamper/alarm
With storing
On
Line/battery/battery failure
Without storing
The cancel buzzer push-button makes it possible to reset the buzzer manually. To do so, press the push-
button at least for 3 seconds with a suitable object.
* Not available at module bus participants (door module, input module, output module, in/output module).
Meaning of the LEDs of AC readers
LED colour
Basic state
After reading a data carrier
Meaning
yellow
on
Ready to read
yellow
off
- Device is dead voltage
- Controller is not parapeterized
- PIN- or door code entry is active
yellow
flashing
Reader is not allocated to any door
green
on
Permanent release
red
on
Permantent blocked
green
on
Door release
red
on
ID card not authorized
red
flashing
Read error
Additionally, the key and LED functions of the macro control of IQ MultiAccess are valid (see separate
manual "Supplementary Functions of IQ MultiAccess", P32205-46-0G0-xx).
Summary of Contents for ACS-8
Page 2: ... VdS Approval Z 105009 class C ...
Page 16: ...16 Installation Instructions ACS 8 ...
Page 28: ...28 Installation Instructions ACS 8 ...
Page 29: ...Installation Instructions ACS 8 29 ...
Page 76: ...76 Installation Instructions ACS 8 Connection component mounting diagram ...
Page 92: ...92 Installation Instructions ACS 8 15 2 ACS 8 Structure ...
Page 122: ...122 Installation Instructions ACS 8 Connection diagram for 026064 Keypad sm plastic housing ...
Page 123: ...Installation Instructions ACS 8 123 ...
Page 124: ...124 Installation Instructions ACS 8 ...
Page 130: ...130 Installation Instructions ACS 8 ...
Page 140: ...140 Installation Instructions ACS 8 ...