30
Installation Instructions / ACS-8
Table 1:
Current consumption of the individual module bus components
Device
Item no.
Minimum power
supply in Volt
max. current
consumption without
peripheral devices
(mA)
ACS-8 without interface card and without
peripheral devices
026580
10
400
Communication module
026587
will be supplied
internally
150
Input module 4I
026590
9
140
Output module 4O
026591
9,5
250
Input / output module 4I/2O
026592
10
230
Potential sparation module
026595.10
10
120
Door module 12V incl. interface without
peripheral devices
026593.10
10
250
Fail secure door strike
(device with load current function) depending on type
120 - 230
Readers
proX
Contactless reader, extended range
026366.00
026366.10
11
400 + 12/LED
Contactless reader, s.m. with keypad
026383.00
10
50 + 12/LED
Contactless reader, f.m.
026387.00
10
50 + 30/LED
Contactless reader, s.m.
026390.00
026390.10
10
50 + 12/LED
Summary of Contents for ACS-8
Page 2: ... VdS Approval Z 105009 class C ...
Page 16: ...16 Installation Instructions ACS 8 ...
Page 28: ...28 Installation Instructions ACS 8 ...
Page 29: ...Installation Instructions ACS 8 29 ...
Page 76: ...76 Installation Instructions ACS 8 Connection component mounting diagram ...
Page 92: ...92 Installation Instructions ACS 8 15 2 ACS 8 Structure ...
Page 122: ...122 Installation Instructions ACS 8 Connection diagram for 026064 Keypad sm plastic housing ...
Page 123: ...Installation Instructions ACS 8 123 ...
Page 124: ...124 Installation Instructions ACS 8 ...
Page 130: ...130 Installation Instructions ACS 8 ...
Page 140: ...140 Installation Instructions ACS 8 ...