Section V. Parameter Function Table
57
F4.12
Terminal UP/DOWN variation
rate
0.01Hz/s~65.535Hz/s
1.00Hz/s
☆
It is used to set the frequency variation rate (frequency variation per second) when adjusting the set
frequency with terminals UP/DOWN.
When F0.22 (frequency decimal point) is set to 2, range of F4.12 value is 0.001Hz/s~65.535Hz/s.
When F0.22 (frequency decimal point) is set to 1, range of F4.12 value is 0.01Hz/s~655.35Hz/ s.
F4.13
AI curve 1 minimum input
0.00V~F4.15
0.00V
☆
F4.14
AI curve 1 minimum input
corresponding setup
-100.00%~100.0%
0.0%
☆
F4.15
AI curve 1 maximum input
F4.13~10.00V
10.00V
☆
F4.16
AI curve 1 maximum input
corresponding setup
-100.00%~100.0%
100.0%
☆
F4.17
AI1 filter time
0.00s~10.00s
0.10s
☆
100%
Corresponding setting
(
frequency,torque
)
0V(0mA)
10V(20mA)
A1
100%
0V(0mA)
10V(20mA)
A1
-100%
Corresponding setting
(
frequency
,
torque
)
Fig. 5-10 Relationship between analog input and setup value
The parameters mentioned above define the relationship between analog input voltage and the analog
input setup value.