Section V. Parameter Function Table
61
Low level valid
1
1000
bit
X9 terminal valid state setup
High level valid
0
Low level valid
1
1000
0bit
X10 terminal valid state setup
High level valid
0
Low level valid
1
It is used to set digital input terminal effective mode.
High level valid
:
Connection between COM and corresponding DI is valid,disconnection invalid.
Low level valid
:
Connection between COM and corresponding DI is invalid,disconnection valid.
5.7 Output terminal
:
F5.00-F5.22
HV610C series inverter provides two multifunctional analog terminal output selections, 1
multifunctional relay output terminal, 1 multifunctional DO output terminal, 1 FM terminal (can be
used as high speed pulse output terminal as well as open collector switching output). If the
above output terminals can not meet the field application, users should choose optional multi-
function input/output expansion card.
Code
Description/
Keyboard Display
Setting Range
Factory
Setting
Change
Limit
F5.00
FM terminal output mode
selection
Pulse output(FMP)
0
0
☆
Switch output(FMR)
1
FM is programmable multiplex terminal, which can be used as high speed pulse output terminal (FMP)
or open collector switching output terminal (FMR).
When F5.00 is set to 0, maximum output frequency can reach 10kHz , please refer to F5.06 for related
description.
F5.01
FMR selection (open
collector output terminal)
0-46
0
☆
F5.02
Relay output selection
(TA.TB.TC)
0-46
2
☆
F5.03
Reserved
Reserved
0
☆
F5.04
DO output selection(open
collector output terminal)
0-46
1
☆
F5.03
Reserved
Reserved
0
☆