Section V. Parameter Function Table
99
mode
AI2
2
AI3
3
PULSE
4
PID
5
Preset frequency(F0.08) reference,
UP/DOWN can be modified
6
It is used to select the reference channel of MS speed 0.
Besides choosing FC.00, MS command 0 has many other options, which is convenient for switching
between MS command and other set modes.
Both MS command and simple PLC used as frequency source can easily realize switching between
the two frequency sources.
5.15 Communication function group
:
Fd.00-Fd.06
Code
Description/
Keyboard Display
Setting Range
Factory
Setting
Change
Limit
Fd.00
Baudrate
1bit
MODBUS
6005
☆
300BPS
0
600BPS
1
1200BPS
2
2400BPS
3
4800BPS
4
9600BPS
5
19200BPS
6
38400BPS
7
57600BPS
8
115200BPS
9
10bit
Profibus-DP
115200BPS
0
208300BPS
1
256000BPS
2
512000BPS
3
100
bit
Reserved
1000
bit
Reserved
Fd.01
Dataformat
None parity check (8-N-2)
0
0
☆
Even parity check (8-E-1)
1
Odd parity check(8-O-1)
2