Section V. Parameter Function Table
55
1
:
Two-line mode 2
:
In this operation mode,X1 terminal function is to enable operation,while X2 terminal function is to
determine running direction. The descriptions on the terminal running command are as shown as below
:
Terminal
Set value
Description
X1
1
Forward(FWD)
X2
2
Reverse(REV)
Among them
,
X1
、
X2 are X1~X10 multi-function input terminal, level valid
0 invalid
,
1 valid
K1
K2
Command
0
0
Stop
0
1
Stop
1
0
Forward(FWD)
1
1
Reverse(REV)
Fig. 5-7 Two-line control mode 2
2
:
Three-line mode1
In this operation mode, X3terminal is the enable terminal, running direction controlled by X1terminal
、
X2terminal. The descriptions on the terminal running command are as shown as below
:
Terminal
Set value
Description
X1
1
Forward(FWD)
X2
2
Reverse(REV)
X3
3
Three-line running control
When in the need of running, users should first connect X3 terminal. Forward and reverse running is
realized through the rising edge of X1 or X2.
When in the need of stop, user should disconnect X3 terminal to meet the need. Among them, X1
、
X2
、
X3 are multi-function input terminal of X1~X10. X1,X2 are of pulse valid, while X3 level valid.
0 invalid. 1 valid. X arbitrarily
SB1
SB2
SB3
Command
0
X
X
Stop
1
1
0
Forward(FWD)
1
0
1
Reverse(REV)
1
1
0->1
Reverse(REV)
1
0->1
1
Forward(FWD)
K2
K1
X1 (FWD)
X2 (REV)
COM
HV610C