Section V. Parameter Function Table
86
100bit Reserved
1000
bit
Motor overheating(Fault No.25= Err45)
(Same with F9.47 1 bit)
10000
bit
Runing time arrival(Fault No.26= Err26)
(Same with F9.47 1 bit)
F9.49
Fault protection action
selection 3
1bit
User-defined fault 1(Fault No.27= Err27)
(Same with F9.47 1 bit)
00000
☆
10bit
User-defined fault 2(Fault No.28= Err28)
(Same with F9.47 1 bit)
100bit
Power-on time arrival(Fault No.29= Err29)
(Same with F9.47 1 bit)
1000
bit
Load off(Fault No.30= Err30)
Free stop
0
Stop according to stop mode
1
Decelerate to 7% of motor rated frequency.
Automatically recover to the set frequency if
no load off.
2
10000
bit
PID feedback lost during operation(Fault
No.31= Err31) (Same with F9.47 1 bit)
F9.50
Fault protection action
selection 4
1bit
Excessive speed deviation(Fault No.42=
Err42) (Same with F9.47 1 bit)
00000
☆
10bit
Motor super velocity (Fault No.43=
Err43)(Same with F9.47 1 bit)
100bit
Initial position fault(Fault No.51= Err51)
(Same with F9.47 1 bit)
1000
bit
Reserved
10000
bit
Reserved
If it is set to “free stop”, inverter displays E.****,and stop directly.
If it is set to “stop according to stop mode”, inverter displays A.****, and stop according to the set
stop mode. Inverter displays E.**** after stopped.
If it is set to “keep on running”, inverter displays A.**** and continues running. Running frequency is
set through F9.54.
F9.54
Continued to run when fault
frequency selection
Operation with the current running
frequency
0
0
☆
Operation with the set frequency
1
Operation with the upper limit frequency
2
Operation with the lower limit frequency
3
Operation with the abnormal backup
frequency
4
F9.55
Abnormal backup frequency
60.0%~100.0%
100.0%
☆
When fault occurring during inverter operation , and the fault processing mode set to continuing to
run, inverter would display A** and run with the F9.54 set frequency.
When choosing running frequency as abnormal backup frequency, set value of F9.55 is percentage