Section V. Parameter Function Table
75
Output frequency
Hz
t
t
Set frequency
Detection amplitude
ON
ON
Frequency arrival
detection signal
Fig.5-17 Frequency arrival detection amplitude schematic diagram
F8.22
Acc./dec. hopping frequency
validity
Invalid
0
0
☆
Valid
1
It is used to set whether hopping frequency is effective during process of acceleration/deceleration.
F8.22 =1
:
Actual running frequency will skip the setting frequency boundary when running within the
range of hopping frequency.
Output frequency
Hz
t
Hopping frequency 1
Hopping frequency 2
Hopping frequency amplitude
Hopping frequency amplitude
Hopping frequency amplitude
Hopping frequency amplitude
Fig.5-18 Acc./dec. hopping frequency validity schematic diagram
F8.25
Acc. time1 & acc. time 2
frequency switching point
0.00Hz~Maximum frequency
0.00Hz
☆
F8.26
Dec. time1 & dec. time 2
frequency switching point
0.00Hz~Maximum frequency
0.00Hz
☆
It is valid when motor 1 is selected without switching acceleration / deceleration time through DI
terminal. In inverter running process, F8.25 & F8.26 choose different acceleration / deceleration time
according to the running frequency range.
As shown in fig.5-19
: