Section V. Parameter Function Table
63
19
Under-voltage state output
When inverter is in Under-voltage status, it outpus ON
signal.
20
Communication setup
Please refer to communication protocol.
21
Reserved
Reserved
22
Reserved
Reserved
23
Null speed operation 2(Stop with
output)
When inverter output 0Hz , ON signal is output.
When inverter is in stop status, ON signal is output.
24
Total power-on time arrival
When accumulated power-on time(F7.13) exceeds
F8.16 set value, it outputs ON signal.
25
Inspection level of FDT2 frequency Please refer to function code F8.28
、
F8.29 for details.
26
Frequency 1 arrival output
Please refer to function code F8.30
、
F8.31 for details.
27
Frequency 2 arrival output
Please refer to function code F8.32
、
F8.33 for details.
28
Current 1 arrival output
Please refer to function code F8.38
、
F8.39 for details.
29
Current 2 arrival output
Please refer to function code F8.40
、
F8.41 for details.
30
Timing arrival output
When inverter running time reaches the set timming
(F8.42 valid), it outputs ON signal.
31
AI1excessive input
When analog input value AI1 is bigger than F8.46 (AI1
input protection upper limit) or smaller than F8.45(AI1
input protection lower limit), it outpus ON signal.
32
Load off
Inverter in load off status, it outpus ON signal.
33
Reverse running
Inverter in reverse running mode, it outputs ON signal.
34
Zero current state
Please refer to function code F8.28
、
F8.29 for details.
35
Module temperature arrival
When module radiator temperature(F7.07) reaches the
set value of F8.47, it outputs ON signal.
36
Software excessive current
Please refer to function code F8.36
、
F8.37 for details.
37
Frequency lower limit arrival(stop
with output)
When running frequency reaches frequency lower limit,
it outputs ON signal.When in stop status ,it outputs ON
signal too.
38
Alarm output
When inverter fault with processing mode of continue
running, it outputs alarm signal.
39
Motor over temperature alarm
When motor temperature reaches F9.58 , it outputs ON
signal.(temperature can be viewed through U0.34)
40
The running time arrival
When the running time exceeds the set value of F8.53 ,
it outputs ON signal.
41
Alarm output
When inverter fault with processing mode of continue
running(uninclude under voltage fault), it outputs alarm
signal.
42
running command status output
running command status direct output
(
run
command
)
43
Forward running command
status output
Forward running command status direct output
(
forward run command
)
44
Reverse running command
status output
Reverse running command status direct output
(
Reverse run command
)
46
Relay function
Braking for lifting movement