Section V. Parameter Function Table
113
A6.07
AI curve 4 maximum input
corresponding setup
-100.0%~100.0%
100.0%
☆
A6.08
AI curve 4 minimum input
-10.00V~A6.10
-10.00V
☆
A6.09
AI curve 5 minimum input
corresponding setup
-100.0%~100.0%
-100.0%
☆
A6.10
AI curve 5 inflection point 1
input
A6.08~A6.12
-3.00V
☆
A6.11
AI curve 5 inflection point 1
input corresponding setup
-100.0%~100.0%
-30.0%
☆
A6.12
AI curve 5 inflection point 2
input
A6.10~A6.14
3.00V
☆
A6.13
AI curve 5 inflection point 2
input corresponding setup
-100.0%~100.0%
30.0%
☆
A6.14
AI curve 5 maximum input
A6.12~10.00V
10.00V
☆
A6.15
AI curve 5 maximum input
corresponding setup
-100.0%~100.0%
100.0%
☆
Function of curve 4 and curve 5 are similar with curve 1~curve 3’s. Curve 1~curve 3 are straight
lines, while curve 4 and curve 5 are 4-point curves which could realize more flexible correspondence.
100%
Analog input
corresponding setting
AI maximum input
corresponding setting
AI inflection point 1
corresponding setting
0V(0mA)
AI inflection point 2
corresponding setting
AI minimum input
corresponding setting
AI inflection point 1
10V(20mA)
AI input voltage
-100%
AI inflection point 2
Fig.5-32Curve4 and curve 5 schematic diagram
Notice
:
When setting curve 4 and curve 5, minimum input voltage, inflection point 1 voltage,
inflection point 2 voltage and maximum voltage must be increased in turn.
A6.24
AI1 set hopping point
-100.0%~100.0%
0.0%
☆
A6.25
AI1 set hopping amplitude
0.0%~100.0%
0.5%
☆
A6.26
AI2 set hopping point
-100.0%~100.0%
0.0%
☆
A6.27
AI2 set hopping amplitude
0.0%~100.0%
0.5%
☆
A6.28
AI3 set hopping point
-100.0%~100.0%
0.0%
☆
A6.29
AI3 set hopping amplitude
0.0%~100.0%
0.5%
☆