Section V. Parameter Function Table
53
stop process. This function is used for inverter fast stop ,
which can meet the stop need in system emergency.
48
External stop terminal 2
This terminal can be used to stopthe inverter in any
circumstances (panel control ,terminal control and
communication control). Deceleration time is fixed to
deceleration time 4.
49
Deceleration DC braking
If it is valid, inverter first decelerates to stop DC braking
start frequency and then switches to DC braking state.
50
Running time reset
Inverter running time of this time is cleared if the terminal is
valid. It operates with the use of F8.42 and F8.53.
Schedule 1 MS command function description
4 MS command terminals, which can be combined into 16 states. For 16 corresponding values, please
refer to schedule 1 as below
:
K4
K3
K2
K1
Command setup
Corresponding
parameter
OFF
OFF
OFF
OFF
MS command 0
FC.00
OFF
OFF
OFF
ON
MS command 1
FC.01
OFF
OFF
ON
OFF
MS command 2
FC.02
OFF
OFF
ON
ON
MS command 3
FC.03
OFF
ON
OFF
OFF
MS command 4
FC.04
OFF
ON
OFF
ON
MS command 5
FC.05
OFF
ON
ON
OFF
MS command 6
FC.06
OFF
ON
ON
ON
MS command 7
FC.07
ON
OFF
OFF
OFF
MS command 8
FC.08
ON
OFF
OFF
ON
MS command 9
FC.09
ON
OFF
ON
OFF
MS command 10
FC.10
ON
OFF
ON
ON
MS command 11
FC.11
ON
ON
OFF
OFF
MS command 12
FC.12
ON
ON
OFF
ON
MS command 13
FC.13
ON
ON
ON
OFF
MS command 14
FC.14
ON
ON
ON
ON
MS command 15
FC.15
When frequency source is set to multi-stage speed mode, 100.0% of function code FC.00~FC.15 are
corresponding to maximum frequency F0.10. To meet the need, MS command can be used not only for
multi-stage speed function, but also PID setup source or VF separation voltage source.
Schedule 2 Acceleration / deceleration terminal selection description
:
Terminal2 Terminal1
Acc./dec. selection
Corresponding
parameter
OFF
OFF
Acc./dec. time 1
F0.17
、
F0.18
OFF
ON
Acc./dec. time 2
F8.03
、
F8.04
ON
OFF
Acc./dec. time 3
F8.05
、
F8.06
ON
ON
Acc./dec. time 4
F8.07
、
F8.08