Section V. Parameter Function Table
60
This function code is used to determine analog quantity corresponding setup when analog input
voltage below the setup of minimum input.
The 1bit, 10bit, 100bit of the function code are corresponding to the analog input AI1
、
AI2
、
AI3
respectively. If the bit is set to 0 and AI is below the minimum setup , the analog input setup is the curve
“minimum input corresponding setup”(F4.14
、
F4.19
、
F4.24) . If the bit is set to 0 and AI is below the
minimum setup , the analog quantity corresponding setup is 0.0%.
F4.35
X1 delay time
0.0s~3600.0s
0.0s
★
F4.36
X2 delay time
0.0s~3600.0s
0.0s
★
F4.37
X3 delay time
0.0s~3600.0s
0.0s
★
Only X1, X2, X3 are able to set equipment delay time.
They are used to set delay time to inverter DI terminal state change.
F4.38
DI terminal effective mode
selection 1
1bit
X1 terminal valid state setup
00000
★
High level valid
0
Low level valid
1
10bit
X2 terminal valid state setup
High level valid
0
Low level valid
1
100bit X3 terminal valid state setup
High level valid
0
Low level valid
1
1000
bit
X4 terminal valid state setup
High level valid
0
Low level valid
1
1000
0bit
X5 terminal valid state setup
High level valid
0
Low level valid
1
F4.39
DI terminal effective mode
selection 2
1bit
X6 terminal valid state setup
00000
★
High level valid
0
Low level valid
1
10bit
X7 terminal valid state setup
High level valid
0
Low level valid
1
100bit X8 terminal valid state setup
High level valid
0