Chapter 2 Installation and Wiring
2 - 18
Terminal layout
Inverter model
R
(L1)
S
(L2)
T
(L3)
PD
(+1)
P
(+)
N
(-)
U
(T1)
V
(T2)
W
(T3)
R0 T0
charge lump
G
G
SJ700-550LFF2
R0 and T0: M4
Ground terminal:
M8
Other terminals:
M10
When not using the DCL,
do not remove the jumper
from terminals PD and P.
Ground terminal with
jumper (shaded in the
figure) to enable/disable the
EMC filter function
Jumper connecting
Terminals PD and P
G
[Method of enabling/disabling the EMC filter function]
Disabling the EMC filter (factory setting)
Enabling the EMC filter
Reference: Leakage current by inverter with model EMC filter enabled or disabled (reference data)
The table below lists the reference currents that may leak from the inverter when the internal EMC filter is enabled or disabled.
(Leakage current is in proportion to the voltage and frequency of input power.)
Note that the values listed in the table below indicate the reference currents leaking from the inverter alone. The values exclude
current leakage from external devices and equipment (e.g., power cables).
200 V class model (input power: 200 VAC, 50 Hz) 400 V class model (input power: 400 VAC, 50 Hz)
5.5kW
~
11kW 15kW
~
37kW 45kW
~
55kW 5.5kW
~
11kW 15kW
~
37kW 45kW
~
55kW
Internal EMC filter enabled
Ca 48mA
Ca 23mA
Ca 23mA
Ca.95mA
Ca.56mA
Ca.56mA
Internal EMC filter disabled
Ca.0.1mA Ca.0.1mA Ca.0.1mA Ca.0.2mA Ca.0.2mA Ca.0.2mA
Summary of Contents for SJ700-055HFF2
Page 15: ...Contents xiii Appendix Appendix A 1 Index Index Index 1 ...
Page 17: ......
Page 22: ......
Page 43: ...Chapter 2 Installation and Wiring 2 21 ...
Page 48: ......
Page 51: ...Chapter 3 Operation 3 3 ...
Page 63: ......
Page 152: ...Chapter 4 Explanation of Functions 4 89 H034 H234 ...
Page 161: ...Chapter 4 Explanation of Functions 4 98 ...
Page 219: ...Chapter 4 Explanation of Functions 4 156 ...
Page 232: ......
Page 244: ......
Page 252: ......
Page 258: ...Chapter 7 Specifications SJ700 550 LFF2 LFUF2 5 Cable hole φ41 7 6 ...
Page 260: ......