Chapter 4 Explanation of Functions
4.4.2 Communication in Modbus-RTU mode
(1) Communication protocol
The communication between the inverter (slave) and external control system (master) is based on the
following protocol:
(2)
(1)
(1)
4 - 132
External control system
Waiting time (silent in
communication wait time [C078])
(3) Communication trip limit time (C077)
(If reception timeout occurs, the inverter will
operate according to the setting of the
operation selection after communication
error [C076].)
Time
Inverter
(1): Query frame that is sent from the external control system to the inverter
(2): Response frame that is sent from the inverter to the external control system
(3): Communication trip limit time (C077)
If the inverter cannot complete the reception of a query from the master system (external control
system) within the communication trip limit time, after having sent a response to the preceding query,
the inverter enters the status in which to receive the query from the beginning. Subsequently, the
inverter returns no response to the master system.
After reception timeout occurs, the inverter operates according to the setting of the selection of
operation after communication error (C076). For details, see the table below. Monitoring of reception
timeout begins when the first communication is performed after the inverter power has been turned
on or the inverter has been reset. Reception timeout is monitored only when the inverter
communicates with the master system.
Item
Function code
Range of data
Description
00: Tripping
The inverter trips (E41) after reception
timeout.
01: Tripping after
stopping the motor
The inverter decelerates and stops the
motor, and then trips (E41) after reception
timeout.
02: Ignoring the errors
The inverter ignores the error without
tripping and alarm output.
03: Stopping the
motor after free-
running (FRS)
The inverter stops the motor after free-
running without tripping and alarm output
after reception timeout.
Selection of operation
after communication error
C076
04: Decelerating and
stopping the motor
The inverter decelerates and stops the
motor without tripping and alarm output after
reception timeout.
Communication trip limit
time setting
C077
0.00 to 99.99 (s)
Limit time to determine the reception timeout
Communication wait time
C078
0. to 1000. (ms)
Time to wait until the inverter starts sending
a response after reception of a query
(excluding the silent interval)
The inverter sends a response (frame (2)) always after receiving a query (frame (1)). The inverter does
not actively output any frame to the external control system.
Summary of Contents for SJ700-055HFF2
Page 15: ...Contents xiii Appendix Appendix A 1 Index Index Index 1 ...
Page 17: ......
Page 22: ......
Page 43: ...Chapter 2 Installation and Wiring 2 21 ...
Page 48: ......
Page 51: ...Chapter 3 Operation 3 3 ...
Page 63: ......
Page 152: ...Chapter 4 Explanation of Functions 4 89 H034 H234 ...
Page 161: ...Chapter 4 Explanation of Functions 4 98 ...
Page 219: ...Chapter 4 Explanation of Functions 4 156 ...
Page 232: ......
Page 244: ......
Page 252: ......
Page 258: ...Chapter 7 Specifications SJ700 550 LFF2 LFUF2 5 Cable hole φ41 7 6 ...
Page 260: ......