Chapter 4 Explanation of Functions
4.2.33 Start frequency setting
b082: Start frequency adjustment
Related code
The start frequency setting function allows you to specify the inverter
output frequency that the inverter initially outputs when an operation
command is input.
Use this function mainly to adjust the start torque.
If the start frequency (b082) is set too high, the inverter will start the motor with a full voltage, which will
increase the start current. Such status may trigger the overload restriction operation or make the inverter
prone to easily tripping because of the overcurrent protection.
Specifying "04" (0SLV: 0Hz-range sensorless vector control) or "05" (V2: vector control with sensor) for the
V/F characteristic curve selection (A044) disables the start frequency setting function.
Item
Function code
Range of data
Description
Start frequency
adjustment
b082
0.10 to 9.99 (Hz)
Setting of the start frequency
FW
requency
age
b082
Output f
Output volt
4.2.34 Reduced voltage start function
b036: Reduced voltage start selection
b082: Start frequency adjustment
Related code
The reduced voltage start function enables you to make the inverter
increase the output voltage gradually when starting the motor.
Set a small value for the reduced voltage start selection (b036) if you
intend to increase the start torque. On the other hand, setting a small
value will cause the inverter to perform full-voltage starting and to easily
trip because of overcurrent.
Item
Function code
Range of data
Description
00
Disabling the reduced voltage starting
Reduced voltage start
selection
b036
01 to 255
01: Short (about 6 ms)
255: Long (about 1.53 s)
00
01 06
・・・
Reduced Voltage Start
b036
Start frequency
b082
FW
Output frequency
Output voltage
4 - 4
2
Summary of Contents for SJ700-055HFF2
Page 15: ...Contents xiii Appendix Appendix A 1 Index Index Index 1 ...
Page 17: ......
Page 22: ......
Page 43: ...Chapter 2 Installation and Wiring 2 21 ...
Page 48: ......
Page 51: ...Chapter 3 Operation 3 3 ...
Page 63: ......
Page 152: ...Chapter 4 Explanation of Functions 4 89 H034 H234 ...
Page 161: ...Chapter 4 Explanation of Functions 4 98 ...
Page 219: ...Chapter 4 Explanation of Functions 4 156 ...
Page 232: ......
Page 244: ......
Page 252: ......
Page 258: ...Chapter 7 Specifications SJ700 550 LFF2 LFUF2 5 Cable hole φ41 7 6 ...
Page 260: ......