Chapter 8 List of Data Settings
8 - 3
8.4 Extended Function Mode
Default
Code
Function name
Monitored data or setting
_FF
_FEF
_FUF
Setting
during
operation
(allowed or
not)
Change
during
operation
(allowed or
not)
Page
A001
Frequency source setting
00 (keypad potentiometer) (*1), 01 (control circuit terminal block), 02 (digital
operator), 03 (RS485), 04 (option 1), 05 (option 2), 06 (pulse-string input), 07
(easy sequence), 10 (operation function result)
02 01 01
¯
¯
4-8
A002
Run command source setting
01 (control circuit terminal block), 02 (digital operator), 03 (RS485), 04 (option
1), 05 (option 2)
02 01 01
¯
¯
4-8
A003
Base frequency setting
30. to "maximum frequency " (Hz)
60.
50.
60.
¯
¯
A203
Base frequency setting, 2nd
motor
30. to "maximum frequency, 2nd motor" (Hz)
60. 50. 60.
¯
¯
A303
Base frequency setting, 3rd
motor
30. to "maximum frequency, 3rd motor" (Hz)
60. 50. 60.
¯
¯
4-11
A004
Maximum frequency setting
30. to 400. (Hz)
60.
50.
60.
¯
¯
A204
Maximum frequency setting, 2nd
motor
30. to 400. (Hz)
60. 50. 60.
¯
¯
Basic set
tings
A304
Maximum frequency setting, 3rd
motor
30. to 400. (Hz)
60. 50. 60.
¯
¯
4-11
A005
[AT] selection
00 (switching between O and OI terminals), 01 (switching between O and O2
terminals), 02 (switching between O terminal and keypad potentiometer) (*1),
03 (switching between OI terminal and keypad potentiometer) (*1), 04
(switching between O2 and keypad potentiometer) (*1)
00
¯
¯
A006
[O2] selection
00 (single), 01 (auxiliary frequency input via O and OI terminals)
(nonreversible), 02 (auxiliary frequency input via O and OI terminals)
(reversible), 03 (disabling O2 terminal)
03
¯
¯
4-12
A011
[O]-[L] input active range start
frequency
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯
{
A012
[O]-[L] input active range end
frequency
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
¯
{
A013
[O]-[L] input active range start
voltage
0. to "[O]-[L] input active range end voltage" (%)
0.
¯
{
A014
[O]-[L] input active range end
voltage
"[O]-[L] input active range start voltage" to 100. (%)
100.
¯
{
A015
[O]-[L] input active range start
frequency selection
00 (external start frequency), 01 (0 Hz)
01
¯
{
4-14
A016
External frequency filter time
const.
1. to 30. or 31. (500 ms filter ±0.1 Hz with hysteresis)
31.
¯
{
4-15
Analog input
and o
the
rs
A017
Easy sequence function
selection
00 (disabling), 01 (enabling)
00
¯
¯
4-95
A019
Multispeed operation selection
00 (binary: 16 speeds selectable with 4 terminals), 01 (bit: 8 speeds selectable
with 7 terminals)
00
¯
¯
A020
Multispeed frequency setting
0.0 or “start frequency” to “maximum frequency” (Hz)
0.00
{
{
A220
Multispeed frequency setting,
2nd motor
0.0 or “start frequency” to “maximum frequency, 2nd motor” (Hz)
0.00
{
{
A320
Multispeed frequency setting,
3rd motor
0.0 or “start frequency” to “maximum frequency, 3rd motor” (Hz)
0.00
{
{
A021
Multispeed 1 setting
0.0 or “start frequency” to “1st maximum frequency” (Hz)
0.00
{
{
A022
Multispeed 2 setting
0.0 or “start frequency” to “2nd maximum frequency” (Hz)
0.00
{
{
A023
Multispeed 3 setting
0.0 or “start frequency” to “3rd maximum frequency” (Hz)
0.00
{
{
A024
Multispeed 4 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
{
{
A025
Multispeed 5 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
{
{
A026
Multispeed 6 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
{
{
A027
Multispeed 7 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
{
{
A028
Multispeed 8 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
{
{
A029
Multispeed 9 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
{
{
A030
Multispeed 10 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
{
{
A031
Multispeed 11 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
{
{
A032
Multispeed 12 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
{
{
A033
Multispeed 13 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
{
{
A034
Multispeed 14 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
{
{
A035
Multispeed 15 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
{
{
4-47
A038
Jog frequency setting
"Start frequency" to 9.99 (Hz)
1.00
{
{
M
ult
ispeed ope
rat
ion
an
d jogging
A039 Jog
stop
mode
00 (free-running after jogging stops [disabled during operation]), 01
(deceleration and stop after jogging stops [disabled during operation]), 02 (DC
braking after jogging stops [disabled during operation]), 03 (free-running after
jogging stops [enabled during operation]), 04 (deceleration and stop after
jogging stops [enabled during operation]), 05 (DC braking after jogging stops
[enabled during operation])
00
¯
{
4-49
*1 This setting is valid only when the OPE-SR is connected.
Summary of Contents for SJ700-055HFF2
Page 15: ...Contents xiii Appendix Appendix A 1 Index Index Index 1 ...
Page 17: ......
Page 22: ......
Page 43: ...Chapter 2 Installation and Wiring 2 21 ...
Page 48: ......
Page 51: ...Chapter 3 Operation 3 3 ...
Page 63: ......
Page 152: ...Chapter 4 Explanation of Functions 4 89 H034 H234 ...
Page 161: ...Chapter 4 Explanation of Functions 4 98 ...
Page 219: ...Chapter 4 Explanation of Functions 4 156 ...
Page 232: ......
Page 244: ......
Page 252: ......
Page 258: ...Chapter 7 Specifications SJ700 550 LFF2 LFUF2 5 Cable hole φ41 7 6 ...
Page 260: ......