Chapter 3 Operation
- Use the and/or key to change the displayed value to "00" for forward operation or "01" for
reverse operation, and then press the key once to determine the operation direction.
1
2
STR
(The display reverts to [F004].)
7) Set the monitor mode.
- To monitor the output frequency, display the function code "d001", and then press the key once.
FUNC
(The monitor shows the output frequency.)
To monitor the operation direction, display the function code "d003", and then press the key
once.
FUNC
(The monitor shows for forward operation, for reverse operation, or for stopping.)
8) Press the key to start the motor.
(The RUN lamp [green LED] goes on.)
RUN
9) Press the key to decelerate or stop the motor.
(When the motor stops, the RUN lamp [green LED] goes off.)
STOP/
RESET
- During the test run, confirm that the inverter does not trip while accelerating or decelerating the motor
and that the motor speed and frequencies are correct.
-
If a trip due to overcurrent or overvoltage has occurred during the test run, increase the acceleration
and deceleration time.
-
Make sure that there is enough margin to trip level by monitoring the output current (d002) and DC
voltage (d102).
3 - 12
Summary of Contents for SJ700-055HFF2
Page 15: ...Contents xiii Appendix Appendix A 1 Index Index Index 1 ...
Page 17: ......
Page 22: ......
Page 43: ...Chapter 2 Installation and Wiring 2 21 ...
Page 48: ......
Page 51: ...Chapter 3 Operation 3 3 ...
Page 63: ......
Page 152: ...Chapter 4 Explanation of Functions 4 89 H034 H234 ...
Page 161: ...Chapter 4 Explanation of Functions 4 98 ...
Page 219: ...Chapter 4 Explanation of Functions 4 156 ...
Page 232: ......
Page 244: ......
Page 252: ......
Page 258: ...Chapter 7 Specifications SJ700 550 LFF2 LFUF2 5 Cable hole φ41 7 6 ...
Page 260: ......