Chapter 4 Explanation of Functions
4.3.14 Multistage position switching function (CP1/CP2/CP3)
- When functions "66" (CP1) to "68" (CP3) are assigned to terminal [1] function (C001) to terminal [8]
function (C008), you can select a position setting from multistage positions 0 to 7.
- Use multistage position settings 0 to 7 (P060 to P067) for the position settings.
-
If no position settings are assigned to terminals, multistage position setting 0 (P060) is assumed.
Position
setting CP3 CP2 CP1
Multistage position setting 0
0
0
0
Multistage position setting 1
0
0
1
Multistage position setting 2
0
1
0
Multistage position setting 3
0
1
1
Multistage position setting 4
1
0
0
Multistage position setting 5
1
0
1
Multistage position setting 6
1
1
0
- You can specify a delay to be applied at multistage position setting input, until the relevant terminal input
is determined. Use this specification to prevent the application of fluctuating terminal input before it is
determined.
- You can adjust the determination time with the multistage speed/position determination time setting
(C169). The input data is finally determined when the terminal input becomes stable after the delay set as
C169. (Note that a long determination time deteriorates the input terminal response.)
CP1
CP2
CP3
Position command
Determination time (C169) specified
4
1
5
3
Determination time (C169) = 0
7
4 - 11
1
4.3.15 Speed/position switching function (SPD)
Determination time
(C169)
- To perform speed control operation in absolute position control mode, turn on the SPD terminal.
- While the SPD terminal is off, the current position count remains at 0. Therefore, if the SPD terminal is
turned off during operation, the control operation is switched to position control operation based on the
position where the terminal is turned off. (Speed control operation is switched to position control
operation.)
- If the position setting is 0 at this time, the inverter stops the motor at that position.
(Hunting may occur if a certain position loop gain value has been set.)
- While the SPD terminal is on, the rotating direction depends on the operation command. When
switching from speed control to position control, pay attention to the sign of the value set in the operation
command.
Output frequency
Position control
Speed control
Time
Start of position counting
Target position
ON
SPD terminal
Summary of Contents for SJ700-055HFF2
Page 15: ...Contents xiii Appendix Appendix A 1 Index Index Index 1 ...
Page 17: ......
Page 22: ......
Page 43: ...Chapter 2 Installation and Wiring 2 21 ...
Page 48: ......
Page 51: ...Chapter 3 Operation 3 3 ...
Page 63: ......
Page 152: ...Chapter 4 Explanation of Functions 4 89 H034 H234 ...
Page 161: ...Chapter 4 Explanation of Functions 4 98 ...
Page 219: ...Chapter 4 Explanation of Functions 4 156 ...
Page 232: ......
Page 244: ......
Page 252: ......
Page 258: ...Chapter 7 Specifications SJ700 550 LFF2 LFUF2 5 Cable hole φ41 7 6 ...
Page 260: ......