Chapter 8 List of Data Settings
8 - 13
Default
Code
Function name
Monitored data or setting
_FF _FEF
_FUF
Setting
during
operation
(allowed or
not)
Change
during
operation
(allowed or
not)
Page
H001 Auto-tuning
Setting
00 (disabling auto-tuning), 01 (auto-tuning without rotation), 02 (auto-tuning
with rotation)
00
¯
¯
H002
Motor data selection, 1st motor
00 (Hitachi standard data), 01 (auto-tuned data),
02 (auto-tuned data [with online auto-tuning function])
00
¯
¯
H202
Motor data selection, 2nd motor
00 (Hitachi standard data), 01 (auto-tuned data),
02 (auto-tuned data [with online auto-tuning function])
00
¯
¯
H003
Motor capacity, 1st motor
0.20 to 75.00 (kW)
Factory setting
¯
¯
H203
Motor capacity, 2nd motor
0.20 to 75.00 (kW)
Factory setting
¯
¯
H004
Motor poles setting, 1st motor
2, 4, 6, 8, 10 (poles)
4
¯
¯
H204
Motor poles setting, 2nd motor
2, 4, 6, 8, 10 (poles)
4
¯
¯
4-85
H005
Motor speed constant, 1st motor
0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000)
1.590
{
{
H205
Motor speed constant, 2nd motor
0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000)
1.590
{
{
4-89
H006
Motor stabilization constant, 1st
motor
0. to 255.
100.
{
{
H206
Motor stabilization constant, 2nd
motor
0. to 255.
100.
{
{
H306
Motor stabilization constant, 3rd
motor
0. to 255.
100.
{
{
4-79
H020
Motor constant R1, 1st motor
0.001 to 9.999, 10.00 to 65.53 (
Ω
)
Depending on motor capacity
¯
¯
H220
Motor constant R1, 2nd motor
0.001 to 9.999, 10.00 to 65.53 (
Ω
)
Depending on motor capacity
¯
¯
H221
Motor constant R2, 1st motor
0.001 to 9.999, 10.00 to 65.53 (
Ω
)
Depending on motor capacity
¯
¯
H221
Motor constant R2, 2nd motor
0.001 to 9.999, 10.00 to 65.53 (
Ω
)
Depending on motor capacity
¯
¯
H222
Motor constant L, 1st motor
0.01 to 99.99, 100.0 to 655.3 (mH)
Depending on motor capacity
¯
¯
H222
Motor constant L, 2nd motor
0.01 to 99.99, 100.0 to 655.3 (mH)
Depending on motor capacity
¯
¯
H223
Motor constant Io
0.01 to 99.99, 100.0 to 655.3 (A)
Depending on motor capacity
¯
¯
H223
Motor constant Io, 2nd motor
0.01 to 99.99, 100.0 to 655.3 (A)
Depending on motor capacity
¯
¯
H224
Motor constant J
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
Depending on motor capacity
¯
¯
H224
Motor constant J, 2nd motor
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
Depending on motor capacity
¯
¯
4-88
H030
Auto constant R1, 1st motor
0.001 to 9.999, 10.00 to 65.53 (
Ω
)
Depending on motor capacity
¯
¯
H230
Auto constant R1, 2nd motor
0.001 to 9.999, 10.00 to 65.53 (
Ω
)
Depending on motor capacity
¯
¯
H231
Auto constant R2, 1st motor
0.001 to 9.999, 10.00 to 65.53 (
Ω
)
Depending on motor capacity
¯
¯
H231
Auto constant R2, 2nd motor
0.001 to 9.999, 10.00 to 65.53 (
Ω
)
Depending on motor capacity
¯
¯
H232
Auto constant L, 1st motor
0.01 to 99.99, 100.0 to 655.3 (mH)
Depending on motor capacity
¯
¯
H232
Auto constant L, 2nd motor
0.01 to 99.99, 100.0 to 655.3 (mH)
Depending on motor capacity
¯
¯
H233
Auto constant Io, 1st motor
0.01 to 99.99, 100.0 to 655.3 (A)
Depending on motor capacity
¯
¯
H233
Auto constant Io, 2nd motor
0.01 to 99.99, 100.0 to 655.3 (A)
Depending on motor capacity
¯
¯
H234
Auto constant J, 1st motor
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
Depending on motor capacity
¯
¯
Cont
ro
l cons
tan
ts
H234
Auto constant J, 2nd motor
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
Depending on motor capacity
¯
¯
4-85
Summary of Contents for SJ700-055HFF2
Page 15: ...Contents xiii Appendix Appendix A 1 Index Index Index 1 ...
Page 17: ......
Page 22: ......
Page 43: ...Chapter 2 Installation and Wiring 2 21 ...
Page 48: ......
Page 51: ...Chapter 3 Operation 3 3 ...
Page 63: ......
Page 152: ...Chapter 4 Explanation of Functions 4 89 H034 H234 ...
Page 161: ...Chapter 4 Explanation of Functions 4 98 ...
Page 219: ...Chapter 4 Explanation of Functions 4 156 ...
Page 232: ......
Page 244: ......
Page 252: ......
Page 258: ...Chapter 7 Specifications SJ700 550 LFF2 LFUF2 5 Cable hole φ41 7 6 ...
Page 260: ......