Chapter 4 Explanation of Functions
4.2.62 Running time over and power-on time over signals (RNT and ONT)
b034: Run/power-on warning time
C021 to C025: Terminal [11] to [15]
functions
C026: Alarm relay terminal function
d016: Cumulative operation RUN time
monitoring
d017: Cumulative power-on time monitoring
Related code
The inverter outputs the operation time over (RNT) signal or the
plug-in time over (ONT) signal when the time specified as the
run/power-on warning time (b034) is exceeded.
Item
Function code
Range of data
Description
Run/power-on warning time
b034
0.
1. to 9999.
1000 to 6553
Disabling the signal output
Setting in units of 10 hours
Setting in units of 100 hours
(range: 100,000 to 655,300 hours)
(1) Operation time over (RNT) signal
To use this signal function, assign function "11" (RNT) to one of the intelligent output terminals [11] to [15]
(C021 to C025) and the alarm relay terminal (C026).
Specify the run/power-on warning time (b034).
(2) Plug-in time over (ONT) signal
To use this signal function, assign function "12" (ONT) to one of the intelligent output terminals [11] to [15]
(C021 to C025) and the alarm relay terminal (C026).
Specify the run/power-on warning time (b034).
4.2.63 0 Hz speed detection signal (ZS)
4 -
64
The inverter outputs the 0 Hz speed detection signal when the inverter
output frequency falls below the threshold frequency specified as the
zero speed detection level (C063).
To use this signal function, assign function "21" (ZS) to one of the
intelligent output terminals [11] to [15] (C021 to C025) and the alarm relay
terminal (C026).
A044/A244/A344: V/F characteristic
curve selection, 1st/2nd/3rd motors
C021 to C025: Terminal [11] to [15]
functions
C063: Zero speed detection level
Related code
This signal function applies to the inverter output frequency when the V/F characteristic curve selection is
based on the constant torque characteristic (VC), reduced-torque characteristic (1.7th power of VP), free
V/f characteristic, sensorless vector control, or 0Hz-range sensorless vector control. It applies to the motor
speed when the V/F characteristic curve selection is based on the vector control with sensor.
Item
Function code
Data or range of data
Description
Terminal function
C021 to C025
Alarm relay terminal function
C026
21
ZS: 0 Hz speed detection signal
Zero speed detection level
C063
0.00 to 100.0 (Hz)
Setting of the frequency to be
determined as 0 Hz
Summary of Contents for SJ700-055HFF2
Page 15: ...Contents xiii Appendix Appendix A 1 Index Index Index 1 ...
Page 17: ......
Page 22: ......
Page 43: ...Chapter 2 Installation and Wiring 2 21 ...
Page 48: ......
Page 51: ...Chapter 3 Operation 3 3 ...
Page 63: ......
Page 152: ...Chapter 4 Explanation of Functions 4 89 H034 H234 ...
Page 161: ...Chapter 4 Explanation of Functions 4 98 ...
Page 219: ...Chapter 4 Explanation of Functions 4 156 ...
Page 232: ......
Page 244: ......
Page 252: ......
Page 258: ...Chapter 7 Specifications SJ700 550 LFF2 LFUF2 5 Cable hole φ41 7 6 ...
Page 260: ......