Chapter 4 Explanation of Functions
Data Description
Reference
item
Page
53
MJA: Major failure
Major failure signal
4-70
54 WCO
55 WCOI
56 WCO
Window comparators function
4-71
4.2.59 Intelligent output terminal a/b (NO/NC) selection
The intelligent output terminal a/b (NO/NC) selection function
allows you to specify a-contact or b-contact output for each of
the intelligent output terminals [11] to [15] and the alarm relay
terminal.
The intelligent output terminals [11] to [15] are used for open-collector output, and the alarm relay terminal
is used for relay output.
Item Function
code
Data
Description
00
a-contact (NO)
Terminal active state
C031 to C035
01
b-contact (NC)
00
a-contact (NO)
Alarm relay active state
C036
01
b-contact (NC)
- An a-contact turns on the output signal when closed and turns it off when opened.
- A b-contact turns on the output signal when opened and turns it off when closed.
(1) Specifications of intelligent output terminals [11] to [15]
Intelligent output terminals [11] to [15] have the following specifications:
15 CM2
…
…
11
Setting of C031 to C035
Power supply
Output signal
ON
ON
OFF
00
(a-contact)
OFF
-
ON
ON
OFF
01
(b-contact)
OFF
-
(2) Specifications of alarm relay terminal
The alarm relay terminal uses a normally-closed (NC) contact that operates as described below.
AL0 AL1 AL2
Example of operation as an alarm output terminal
Output terminal state
Setting
of C036
Power
supply
Inverter
status
AL1-AL0 AL2-AL0
Error Closed Open
ON
Normal Open Closed
00
OFF
-
Open
Closed
Error Open
Closed
ON
Normal Closed Open
01
(default)
OFF
-
Open
Closed
4 -
6
1
C031 to C035: Terminal [11] to [15] active state
C036: Alarm relay active state
Related code
Electric characteristics
(Between each terminal and CM2)
Voltage drop when turned on: 4 V or less
Allowable maximum voltage: 27 VDC
Allowable maximum current: 50 mA
Inside the
inverter
Resistance load
Inductive load
Maximum contact
capacity
250 VAC, 2 A
30 VDC,
3
A
250 VAC, 2 A
30 VDC, 8 A
AL1-AL0
Minimum contact
capacity
100 V AC, 10 mA
5 VDC, 100 mA
Maximum contact
capacity
250 VAC, 1A
30 VDC, 1A
250 VAC, 0.2 A
30 VDC, 0.2 A
AL2-AL0
Minimum contact
capacity
100 VAC, 10 mA
5 VDC, 100 mA
Inside the
inverter
Summary of Contents for SJ700-055HFF2
Page 15: ...Contents xiii Appendix Appendix A 1 Index Index Index 1 ...
Page 17: ......
Page 22: ......
Page 43: ...Chapter 2 Installation and Wiring 2 21 ...
Page 48: ......
Page 51: ...Chapter 3 Operation 3 3 ...
Page 63: ......
Page 152: ...Chapter 4 Explanation of Functions 4 89 H034 H234 ...
Page 161: ...Chapter 4 Explanation of Functions 4 98 ...
Page 219: ...Chapter 4 Explanation of Functions 4 156 ...
Page 232: ......
Page 244: ......
Page 252: ......
Page 258: ...Chapter 7 Specifications SJ700 550 LFF2 LFUF2 5 Cable hole φ41 7 6 ...
Page 260: ......