GS4000 Installation Guide Revision 4.00
520-10-026-30X
4-23
Step 3
Remove the screws from the 0V terminal, -48V/-60V terminal, and earth (ground)
terminal.
Figure 4.5-6 Removal of the Screws
Step 4
Loosen the screws of the cable clamp.
Figure 4.5-7 Loosening the Cable Clamp
Step 5
Put the DC power cable through the cable clamp, and then secure it with screws in
the order of earth (ground) terminal (first), 0V terminal (second) and –48/-60 terminal (third).
Figure 4.5-8 Fixation of terminals
WARNING: WHEN CONNECTING THE DEVICE TO THE DC POWER SUPPLY, USE THE
EARTH (GROUND) TERMINAL TO AVOID AN ELECTRIC SHOCK OR THE
TROUBLE RELATED TO ELECTRIC NOISES.
Step 6
Mount the DC power cable by fastening the screws of the cable clamp.
Figure 4.5-9 Fixation of DC Power Cable
Cable Clamp
Screws
Screws (M5)
0V Terminal
-48V/-60V Terminal
Ground Terminal
DC Power Cable
Screws
Cable Clamp
0V Terminal
-48V/-60V Terminal
Grond Terminal
Cable Clamp
Screws