13 CONTROL AND SAFETY DEVICES
Compressor protection
The compressor is protected by the following devices and their combinations:
1
Pressure switch: this switch stops the compressor when the discharge pressure exceeds the set value.
2
Oil heater: this band-type heater protects against the formation of foam on the oil during cold starts and remains enabled when the
compressor is at a standstill.
Model
RAS-8FSXN1E
RAS-10FSXN1E
RAS-12FSXN1E
RAS-14FSXN1E
RAS-16FSXN1E
For Compressor
Pressure Switches
Automatic Reset, Non-Adjustable
(each one for each compressor)
High
Cut-Out
MPa
4.15
-0.05
4.15
-0.05
4.15
-0.05
4.15
-0.05
4.15
-0.05
-0.15
-0.15
-0.15
-0.15
-0.15
Cut-In
MPa
3.20 +0.15
3.20+0.15
3.20+0.15
3.20+0.15
3.20+0.15
Fuse Capacity
3N~ 400V 50Hz
A
40 x 2
40 x 2
40 x 2
40 x 2 + 32 x 3
40 x 2 + 32 x 3
Oil Heater
Capacity
W
40.8 x 2
40.8 x 2
40.8 x 2
40.8 x 4
40.8 x 4
CCP Timer
Non-Adjustable
Setting Time
min.
3
3
3
3
3
For DC Fan Module
Fuse Capacity
3N~ 400V 50Hz
A
20 x 1
20 x 1
20 x 1
20 x 1
20 x 1
Model
RAS-5FSXNH(E) RAS-6FSXNH(E) RAS-8FSXNH(E) RAS-10FSXNH(E) RAS-12FSXNH(E)
For Compressor
Pressure Switches
Automatic Reset, Non-Adjustable
(each one for each compressor)
High
Cut-Out
MPa
4.15
-0.05
4.15
-0.05
4.15
-0.05
4.15
-0.05
4.15
-0.05
-0.15
-0.15
-0.15
-0.15
-0.15
Cut-In
MPa
3.20 +0.15
3.20+0.15
3.20+0.15
3.20+0.15
3.20+0.15
Fuse Capacity
3N~ 400V 50Hz
A
40 x 2
40 x 2
40 x 2
40 x 2
40 x 2
Oil Heater
Capacity
W
40.8 x 2
40.8 x 2
40.8 x 2
40.8 x 2
40.8 x 2
CCP Timer
Non-Adjustable
Setting Time
min.
3
3
3
3
3
For DC Fan Module
Fuse Capacity
3N~ 400V 50Hz
A
20 x 1
20 x 1
20 x 1
20 x 1
20 x 1
73
PMML0294A rev.2 - 07/2014
Control and safety devices
ENGLISH
PMML0294A_rev.2_02-2014.indb 73
14/07/2014 12:28:40
Summary of Contents for FSXN1E Series
Page 2: ...PMML0294A_rev 2_02 2014 indb 2 14 07 2014 12 27 46 ...
Page 8: ...PMML0294A_rev 2_02 2014 indb 8 14 07 2014 12 27 48 ...
Page 14: ...PMML0294A_rev 2_02 2014 indb 14 14 07 2014 12 27 58 ...
Page 755: ...PMML0294A_rev 2_02 2014 indb 741 14 07 2014 12 34 59 ...
Page 756: ...Printed in Spain 00000 PMML0294A_rev 2_02 2014 indb 742 14 07 2014 12 34 59 ...