10.6.1 External input/output and function
setting
Start of setting
Turn ON DSW4-No.4. Press PSW1 for 3 seconds or more. “Menu
Mode” will be indicated.
End of setting
Press PSW1 for 3 seconds or more when “Menu Mode” is dis
-
played. The display indication become normal. Turn OFF DSW4
number 4.
N O T E
Release “Menu Mode” after the setting is completed. Otherwise,
the air conditioner may not operate appropriately.
Check mode
"
CHEC
"
For more details, refer to
Checking
of outdoor unit by PCB
in the Service
Manual
External input
and output
"
ioS
"
For the setting mode, refer to
below
Function setting
"
Func
"
For the function setting, refer to
below
Press PSW1 one
Menu Mode
1
External input and output setting
By pressing the push-switches PSW3 ( ) and PSW5 ( ), the
function number can be selected.
PSW4 ( ): forward, PSW2 ( ): backward
Fill out the selected function setting number in the space of the
table as shown.
Example:
Item
SEG2
SEG1
SET
1
Input Setting 1 CN17 (1-2 pin)
i1
1
2 Input Setting 2 CN17 (2-3 pin)
i2
2
3 Input Setting 3 CN18 (1-2 pin)
i3
3
4 Output Setting 1 CN16 (1-2 pin)
o1
1
5 Output Setting 2 CN16 (1-3 pin)
o2
2
(Setting before shipment)
Before shipping, the input/output function settings are specified
to each input/output terminal according to above table. The de
-
tails of function number and external input/output settings are as
shown below.
Setting of external input and output function:
Function
number
Input
Output
1
Fixing heating operation mode
Operation signal
2
Fixing cooling operation mode
Alarm signal
3
Demand stoppage
Compressor ON signal
4
Outdoor fan motor start/stop
Defrost signal
5
Forced stoppage
-
6
Demand current control 40%
-
7
Demand current control 60%
-
8
Demand current control 70%
-
9
Demand current control 80%
-
10
Demand current control 100%
-
11
Low noise setting 1
-
Function
number
Input
Output
12
Low noise setting 2
-
13
Low noise setting 3
-
0
No setting
No setting
The same input/output function setting cannot be set to different
input/output terminals. If set, a setting of larger function number
becomes invalid.
Example: When setting of input 1 and input 2 are same, input 2
will be invalid.
2
Function Setting
By pressing the push-switches PSW3 ( ) and PSW5 ( ), the set
-
ting can be changed.
PSW4 ( ): forward, PSW2 ( ): backward
Refer to the Service Manual for more details.
Fill out the selected function setting number in the space of the
table as shown.
Example:
Item
SEG2
SEG1
SET
1
Circulator function at heating
Thermo-OFF
FA
O
2 Night-Shift (Low noise)
ni
O
3 Cancellation of outdoor ambient
temperature limit
G5
O
4 Defrost for cold area (change of
defrost condition)
Jo
O
5 SLo (fan speed) defrost setting
bJ
O
6 Cancellation of hot start
H
O
7 Priority capacity mode
nU
O
8 Compressor frequency control
target value for cooling
Hc
O
9 Compressor frequency control
target value for heating
Hh
O
10.6 FUNCTION SETTING
66
PMML0294A rev.2 - 07/2014
Electrical wiring
PMML0294A_rev.2_02-2014.indb 66
14/07/2014 12:28:39
Summary of Contents for FSXN1E Series
Page 2: ...PMML0294A_rev 2_02 2014 indb 2 14 07 2014 12 27 46 ...
Page 8: ...PMML0294A_rev 2_02 2014 indb 8 14 07 2014 12 27 48 ...
Page 14: ...PMML0294A_rev 2_02 2014 indb 14 14 07 2014 12 27 58 ...
Page 755: ...PMML0294A_rev 2_02 2014 indb 741 14 07 2014 12 34 59 ...
Page 756: ...Printed in Spain 00000 PMML0294A_rev 2_02 2014 indb 742 14 07 2014 12 34 59 ...