5 USER GUIDE
5-41
Example: When the following link parameter settings are employed, the FL-net module operates as
indicated below:
Node number
: 1
Area 1 address
: 0x000
Area 1 words
: 0x000
Area 2 address
: 0x0000
Area 2 words
: 0x0040
Minimum frame interval
: 30
Node name
: CPU01
Node number
: 3
Area 1 address
: 0x000
Area 1 words
: 0x000
Area 2 address
: 0x0080
Area 2 words
: 0x0040
Minimum frame interval
: 30
Node name
: CPU03
Node number
: 2
Area 1 address
: 0x000
Area 1 words
: 0x000
Area 2 address
: 0x0040
Area 2 words
: 0x0040
Minimum frame interval
: 30
Node name
: CPU02
Node 1
Node 2
Node 3
0000
0040
0080
Node 1
Node 2
Node 3
Area 2
common memory
Node 3 Node 2
Node 1
Token
Node 3 Node 2 Node 1
Token
Received frame
Transmitted frame
3 ms
Time interval between
token reception and
frame transmission
(Reception)
(Reception)
(Reception)
(Reception)
(Reception)
(Reception)
Data is exchanged using the area 2 common memory area as shown above.