5 USER GUIDE
5-78
Communication log data read request: logrd( )
[Linking procedure]
C language
Main Sub
Struct logr_p {
long node ;
unsigned short *Erradr ;
unsigned char
*logadr ;
} ;
long (*Logrd)( ) ;
long rtn ;
struct logr_p *padr ;
Logrd = (long(*)( ))0xD600E0 ;/* S10V */
rtn = (*Logrd)(padr) ;
Struct logr_p {
long node ;
unsigned short *Erradr ;
unsigned char
*logadr ;
} ;
long (*Logrd)( );
long rtn ;
struct logr_p *padr ;
Logrd = (long(*)( ))0xDE00E0 ;/* S10V */
rtn = (*Logrd)(padr) ;
Note: For the S10mini, substitute 0xD7413C, 0xDF413C for 0xD600E0, 0xDE00E0.
[Parameters for mathematical/logical function]
+0x0000
Message transmission service number (10)
+0x0004
Remote node number (1 to 254)
+0x0008
Error code storage address
+0x000C
Log data storage address
~
~
~
~
~
~