5 USER GUIDE
5-59
Enter the settings
for the transparent
reception task and
transparent
reception task’s
factor.
Enter the starting address for the
transparent receiving flag area.
Figure 5-46 Transparent Receiving Flag Area and Transparent
Reception Task Setup Window
The table below shows the acceptable input ranges for the setup items.
Input item
Description
Acceptable setting range
Transparent reception
task
Task number of the task that is to start
upon receipt of a transparent message.
For the S10mini, the acceptable setting
ranges from 1 to 128. However, enter a
setting between 2 and 100. For the S10V,
the acceptable setting ranges from 1 to 255.
Because 230 to 255 are used by the system,
they are not started.
Transparent reception
task’s factor
Factor for starting a transparent reception
task.
S10mini: 0 to 16
S10V: 0 to 32
Transparent receiving
flag area
This area reports a transmission source
node number when a transparent message
is received (the area size is 16 words).
See Table 5-7, “Address Ranges for
Common Memory Area Allocation in CPU
or LPU Memory.”
Note: The symbols and extension memory addresses selectable for a transparent receiving flag
area are the same as for a CPU or LPU memory area. Also, note that a transparent
receiving flag area setting must not be a duplicate of any of those for the other set areas.
Summary of Contents for FL.NET
Page 1: ......
Page 2: ......
Page 29: ...1 OVERVIEW ...
Page 33: ...2 FL NET MODULE ...
Page 42: ...3 FL NET MODULE INSTALLATION ...
Page 46: ...4 FL NET MODULE WIRING PROCEDURES ...
Page 53: ...5 USER GUIDE ...
Page 203: ...5 USER GUIDE 5 151 Sample printout ...
Page 206: ...6 MAINTENANCE ...
Page 210: ...7 TROUBLESHOOTING ...
Page 225: ...8 APPENDIXES ...