5 USER GUIDE
5-54
After a request is issued by the C mode handler, do not make another message request until
the “user request processing in progress” bit is reset. If any message request is issued
before the bit is reset, it is not processed because another message is being processed (the
“message processing already in progress” error code is set at an error code storage address).
After the “user request processing in progress” bit is reset, enter the status prevailing after
the end of the processing at an error code storage address specified at C mode handler
startup.
To check whether the requested processing is ended normally, note the code that is set at the
error code storage address.
Table 5-8 C Mode Handler List
Subroutine call address
Main Sub
Name
S10mini S10V S10mini S10V
Functionality description
wordrd( )
/D74112 /D60020 /DF4112 /DE0020 Issues a word block read request.
wordwt( )
/D74118 /D60040 /DF4118 /DE0040 Issues a word block write request.
parard( )
/D7411E /D60060 /DF411E /DE0060 Issues a network parameter read request.
parawt( )
/D74124 /D60080 /DF4124 /DE0080 Issues a network parameter write request.
reqstop( )
/D7412A /D600A0 /DF412A /DE00A0 Issues a stop request.
reqrun( )
/D74130 /D600C0 /DF4130 /DE00C0 Issues a run request.
logrd( )
/D7413C /D600E0 /DF413C /DE00E0 Issues a communication log read request.
logclr( )
/D74142 /D60100 /DF4142 /DE0100 Issues a communication log clear request.
mesret( )
/D74148 /D60120 /DF4148 /DE0120 Issues a message return request.
reqmacro( ) /D74160 /D60140 /DF4160 /DE0140
Issues a specified-task control request (Hitachi’s unique
transparent type of support).
toukaread( ) /D74178 /D60160 /DF4178 /DE0160
Issues a transparent message reception request (Hitachi’s
unique transparent type of support).
toukasend( ) /D7417E /D60180 /DF417E /DE0180
Issues a transparent message transmission request (Hitachi’s
unique transparent type of support).
comoffset( ) /D74184 /D601A0 /DF4184 /DE01A0 Issues a common memory offset feature request.
Note: For bit allocation for the self-node status flag, see “5.4.6 Using the management tables.”
Do not mix to use C mode handler and mathematical/logical function.
Please be sure to unify either C mode handler or mathematical/logical function
at FL.NET module unit.
When mounting S10V, FL.NET module (LQE500) before Module Rev.B (Ver-
Rev: 0002-0000) doesn’t provide for message communication function (neither
do C mode handler and mathematical/logical function), but provided for cyclic
communication function having applied common memory area. Utilizing
message communication function in combination with S10V, you should use
the module after Module Rev.C (Ver-Rev: 0003-0000).
Moreover, the above-mentioned Ver-Rev is a micro program Ver-Rev of
FL.NET module which is shown on “Module List” of S10V BASE SYSTEM.
Summary of Contents for FL.NET
Page 1: ......
Page 2: ......
Page 29: ...1 OVERVIEW ...
Page 33: ...2 FL NET MODULE ...
Page 42: ...3 FL NET MODULE INSTALLATION ...
Page 46: ...4 FL NET MODULE WIRING PROCEDURES ...
Page 53: ...5 USER GUIDE ...
Page 203: ...5 USER GUIDE 5 151 Sample printout ...
Page 206: ...6 MAINTENANCE ...
Page 210: ...7 TROUBLESHOOTING ...
Page 225: ...8 APPENDIXES ...