8 APPENDIXES
8-64
(12) Coaxial cable ground terminal installation
(a) Applicable ground terminal
For the ground terminal recommended for use with the FL.NET module, see “8.5.1
Ethernet component list.”
(b) Installation procedure
Installing the coaxial cable ground terminal
Figure 8-67 shows how to install the coaxial cable ground terminal. For the coaxial
cable, provide single-point grounding (Class D or higher) with a ground terminal (G-TM).
Ground the coaxial cable at an arbitrary point.
①
Insert the insertion claw into the ground terminal body.
Figure 8-66 Mounting the Insertion Claw in the Ground Terminal Body
②
Mount the ground terminal on a coaxial cable and alternately tighten the M4 screws.
Attach a crimp terminal to either screw. Select only one location on a coaxial
segment so as to provide ease of ground connection.
Shield washer
Spring washer
Shield washer
Spring washer
M4 screw
M4 screw
Ground terminal body
Coaxial cable
Crimp terminal
(Class D grounding with a 5.5 mm
2
wire)
Figure 8-67 Installing the Ground Terminal
Ground terminal body
Insertion claw
Summary of Contents for FL.NET