7 TROUBLESHOOTING
7-15
(3) Module error indications
When an error occurs in the FL.NET module, the LER LED on the module turns ON.
LQE500
FL.NET
LER
RX
TX
MODU
No.
LER LED
Figure 7-2 Module Error Lamp
Note that the LER LED turns ON even when the module has not participated in the network.
Therefore, the LER LED indication is not adequate for judging whether the module is
abnormal.
When the LER LED turns ON, note the CPU module indicator on the S10mini because it
furnishes relevant detailed information.
For details on indicator readouts, see “(2) Error indications to the CPU module.”
In the S10V, error information is collected but no error is indicated to the LPU module. The
collected error information can be referenced from [Error log] of [S10V BASE SYSTEM].
For confirming the collected error information, refer to “S10V USER’S MANUAL BASIC
MODULE (manual number SVE-1-100).”
(4) Communication driver error alarm
The FL.NET module does not indicate an error alarm that is issued by a driver.
(5) Viewing the communication log data
You can view the communication log maintained in the module with the setup tool named
“FL.NET For Windows
®
.”
For detailed operating procedure, see “5.6.7 RAS information.”